• English
    • Nederlands
    • Deutsch
    • Franšais
    • Espa˝ol

ES150-
SERIES.

150 W DC Power Supplies

Unit Voltage range Current range
ES 015-10

0 - 15 V

0 - 10 A

ES 030-5

0 - 30 V

0 - 5 A

ES 075-2

0 - 75 V

0 - 2 A

ES 0300-0.45

0 - 300 V

0 - 0.45 A

Features:

    • Very low output ripple and spikes
    • EMC surpasses CE requirements: low emission & high immunity
    • Excellent dynamic response to load changes
    • Protected against all overload and short circuit conditions
    • Designed for long life at full power

Functionalities:

    • Master/Slave parallel and series operation with voltage and current sharing
    • Voltage and current control with 10-turn potentiometers
    • For laboratory use or optional 19” rack mounting
    • Convection cooling

Specifications:

    • Single phase input
90-265 V AC (48-62 Hz)
    • Active Power Factor Correction 

   (PFC)

:

 

0.99 / 0.83 (at 100% load)

 

    • Efficiency
up to 84% (at full load)
    • Output ripple and spikes
0.5 mVrms / 8 mVpp
    • Regulation
from 5 mV (0-100% load step)
    • Recovery time
from 100 μs (50-100% load step)
    • Programming speed
from 7 ms (10-90%)
    • Analog programming accuracy
from 0.2%
    • Stability output voltage and

   current

:

 

10.10-5 / 10.10-5

 

    • MTBF
500.000 hrs
    • Operating ambient temperature
-20 to +50 °C

Standards:

    • Power supply standard
EN 61204-3
    • Generic Emission
EN 61000-6-3 (EN 55022B)
    • Generic Immunity
EN 61000-6-2
    • Safety
EN 60950 / EN 61010
    • Insulation input / output 
3750 Vrms
    • Protection class
IP20
    • cTÜVus
 

 

 

Dimensions and weight:

Width = half 19"

Height = 66 mm (incl. feet)

Depth = 202 mm

Weight = 1.7 kg

Options:

  • Rear Power Output and Remote Sensing

    Output terminals at the rear panel instead of binding posts at the front panel, includes remote sensing. For more information download the data sheet ES150-series (see pages 1-4, 1-5 & 1-6).

  • Secured Voltage and Current Setting

    For maximum security the settings for CV and CC can be adjusted with a screwdriver only and are protected with a plastic cap from accidental adjusting.

     

  • Increased Output Power

    The conservatively rated unit allows to deliver extra output power with the same reliability. At some derating, either the maximum output voltage or current can be increased by about 10%. For more information contact us or our local distributor.

  • 19" Rack Mounting Adapters

    Rack adapter sets for positioning the ES150 units in a 19" rack. Several mounting options possible. For more information download the data sheet ES150-series (see pages 1-5 & 1-6).

  • Sequencer

    Arbitrary Waveform generator or standalone automation. The sequencer is integrated in the Ethernet controller. For more information download the data sheet Ethernet Interface.

  • Software Control and Interfaces

    Factory installed programming interfaces*: 

      • Ethernet (incl. sequencer)
      • PROFIBUS
      • CANBUS
      • RS232 

     

    External programming interface modules:

      • Ethernet module
      • RS232 module
      • IEEE488 module
      • ISO AMP module

     

    * there is only room for one of the interfaces in a unit, analog programming connector will be removed

Downloads Document format Size
Data sheet ES150-series PDF (Acrobat Reader) 1.2 MB
Data sheet ISO AMP Module PDF (Acrobat Reader) 231.1 KB
Sales Department

T: +31 111 413656
F: +31 111 416919

E: by filling out the contact form

 

Contact form
Product Support

T: +31 111 413656
F: +31 111 416919 

E: by filling out the contact form

 